MAKE IT YOURS
EN54 FireProtect Jeweller sounders and VADs.
Wireless addressable fire alarm sounders and visual alarm devices (VADs)

Standards and certifications
* Ajax shows these marks for the EN54 FireProtect Jeweller sounders and VADs range. Check the linked documentation for the exact version and market.
A fire warning, heard and seen.
EN54 FireProtect Jeweller sounders and VADs bring a fire-system warning to the people in the building. Choose audible, visual or combined signalling to suit the location. Supervised wireless communication, replaceable batteries and remote configuration support installation and ongoing service.
Key features. At a glance.
Full compliance with standards1


Installation on a wall or ceiling




Installation in minutes
with the bundled SmartBracket mounting panel and in-app setup



Configuration and testing in Ajax apps
Audible alarm indication3
with a 100 dB buzzer and 32 selectable tones

Tool-free battery replacement
without enclosure disassembly


5 years of operation
on pre-installed CR123A batteries


Sleek and compact design
in white, black, or red


Built for various conditions
with an IP54-rated enclosure and –10 °C to +60 °C operating range


Informative push notifications


Dismantling protection
with SmartBracket locking
- 1Manufacturer-listed marks for this product range. Exact-model certification and regional conditions are shown above.
- 2In open space.
- 3For Sounder and Sounder/VAD versions only; VAD has no sounder. Up to 100 dB at 1 m depends on the selected tone and settings. The manual identifies tones 1, 2, 3, 6, 7 and 13 as meeting EN 54-3.
Overview of this product range. Features and ratings can differ by version. Ajax product information ↗ · EN54 FireProtect (Sounder/VAD) Jeweller specifications ↗
Protection in real places.








EN54 FireProtect Jeweller sounders and VADs
Every detail has a purpose.
Explore the function, installation and system requirements of EN54 FireProtect Jeweller sounders and VADs.
Loading detail…
Choose how the warning is delivered.
Sounder
An audible fire alarm device with 32 selectable tones. It has no VAD light frame.
A warning that can be heard.

Up to 100 dB at 1 m
Sounder and Sounder/VAD offer 32 tones, with level and pattern selected in Ajax apps. Sounder-equipped devices on the same fire panel synchronise their audible alarm.
100 dB is a maximum for particular tones and settings, not the level of every pattern. The manual identifies tones 1, 2, 3, 6, 7 and 13 as meeting EN 54-3. Verify audibility throughout the planned area.
Plan the light around the space.

Ceiling placement
VAD and Sounder/VAD use a red frame flashing at 0.5 Hz: 90 ms on and 1,910 ms off. Ajax specifies the C-3-8 coverage arrangement for ceiling installation.
Ajax recommends mounting up to 3 m on a ceiling. Check the exact coverage specification, room geometry and visibility as part of the fire design.

Wall placement
The wall arrangement offers an alternative when ceiling installation is unsuitable. Ajax specifies W-2.4-8.2 coverage for wall installation.
Ajax recommends mounting up to 2.4 m on a wall. Sounder-only models do not provide this visual alarm function.
A supervised link to the fire panel.
Jeweller, built in
Two-way Jeweller radio carries commands, alarms and device states to the compatible fire panel. Encryption, authentication and frequency hopping protect the link without a separate radio module.
Up to 1,700 m is an open-space figure. Walls and the installation layout reduce usable range. EN54 Fire ReX can extend the route; survey each link at its final position. Alarm delivery and connection-loss timing depend on the system and its settings.
Replace the batteries. Keep the device.

Four replaceable CR123A batteries
All three alarm types use four pre-installed batteries. Ajax states up to five years with the standard 36-second polling interval; actual life depends on alarm use, settings and conditions.
Low-battery notifications prompt service. The compartment opens without dismantling the enclosure; replace the batteries with the specified type and correct polarity, then test the alarm. The mounting lock may require its release tool.
Make service needs visible.
Connection, mounting and battery status
The fire panel and Ajax apps report device faults, low batteries, tamper events and loss of the radio connection. Room, zone and location details help the service team find the affected device.
Connection-loss detection depends on Jeweller settings. Ajax specifies alarm delivery in as little as three seconds; this is distinct from fault detection. Verify the configured fire response on site.
Mount, configure and test.

Assign it to the fire system
Scan the QR code in Ajax apps and assign the device to the room and fire zone. Use a clear location description and configure the required alarm response.
Requires a compatible Ajax fire CIE and matching regional radio version. This is an alarm output, not a standalone fire detector.
Find the right fire device.
Compare EN54 detectors, EN54 and Type4 sounders and visual alarms, and EN54 Indicator. See what detects a fire, what warns people and what helps locate the alarm.
Compare fire detection and alarms →Every detail, in one place.
Communication
- Jeweller communication technology
- Two-way system communication for the functions specified for this model.
- Radio communication range
- up to 1,700 m Between the device and control and indicating equipment (CIE) or a range extender in an open space.
- Encrypted communication
- Encrypted device communication.
- Frequency hopping
- To prevent radio interference and jamming.
Alarm annunciation
- Alarm type
- acoustic and light A sounder and LED frame.
- Sound volume
- At a distance of 1 m Tone 1: 970 Hz — min 71, max 100 dB; Tone 2: 800 Hz / 970 Hz @ 2 Hz — min 76, max 100 dB; Tone 3: 800–970 Hz @ 1 Hz — min 76, max 96 dB; Tone 6: 554 Hz, 0.1 s / 440 Hz, 0.4 s — min 72, max 92 dB; Tone 7: 500–1200 Hz, 3.5 s / 0.5 s OFF — min 75, max 98 dB; Tone 13: 1200–500 Hz @ 1 Hz — min 75, max 98 dB Adjusted by a PRO or user with admin rights in an Ajax app.
- Sound pattern
- 32 tones
- Sound synchronization
- An audible alarm is automatically synchronized on all devices with a sounder connected to the same CIE.
- Flash frequency
- 90 ms ON / 1,910 ms OFF (cycle duration: 2,000 ms; frequency: 0.5 Hz)
- Alarm annunciation test
- To check the sound and visual alarm signals to ensure fire alarm signals are clearly audible and visible in the premises.
Sabotage protection
- Tamper button
- Fault notification when an attempt is made to remove the device from the mounting panel.
- Lock for SmartBracket
- to secure the device on the SmartBracket mounting panel When locked, the lock secures the device and prevents it from being removed without a special tool.
- Protection against spoofing
- device authentication
- Connection loss detection
- after 36 s Detection time depends on Jeweller settings.
Power supply
- Battery
- 4 × CR123A Pre-installed.
- Tool-free battery replacement
- To replace the batteries, turn the battery compartment cover counterclockwise.
- Reverse polarity protection
- Prevents device damage if the batteries are put in incorrectly.
- Recommended battery type
- Huiderui CR123A; 3 V; 1,600 mAh, LiMnO₂
- Calculated battery life
- up to 5 years
Enclosure
- Dimensions
- 145 × 145 × 51 mm
- Weight
- 561 g
- Operating temperature range
- from –10 °C to +60 °C
- Operating humidity
- up to 80%
- Protection class
- IP54
- Flammability rating
- UL 94 V-0
Revision
- Revision
- 2
What’s in the box
- EN54 FireProtect (Sounder/VAD) Jeweller
- 4 × CR123A battery (pre-installed)
- SmartBracket mounting panel
- Installation kit
- Quick start guide
For your installation
- Selected as part of an installer-reviewed EN54 fire design.
- Confirm the supported control panel, device software and regional radio version; test coverage at the final installation position.
- The device's recommended installation height is up to 3 m on the ceiling and up to 2.4 m on the wall.
- The device is designed for outdoor and indoor use.
- Choose the exact version: sensing, power, casing, pack size or interface details can differ between the listed models.